Turkish Zoning Regulation — Clause Reference

Site coverage and floor area ratios, lifts, stairs, ramps, minimum room sizes and parking demand, with clause numbers. Tables are read live from the calculation engine.

Source: Zoning Regulation — OG 3/7/2017-30113 Parking: OG 22/2/2018-30338 Engine: engine/imar.js Tests: tests/imar.test.js — 32/32 Last verified: 2026-09-13
How this page works The tables are not hand-written; they are read from the data inside engine/imar.js. The same data feeds six calculation tools. Both regulations are public law published in the Official Gazette.

1. Site coverage and floor area ratio — Clauses 4, 22

Site coverage ratio: the ratio of building footprint to plot area. The footprint is computed by taking together the ground-floor projection and all basement storeys that remain above natural or finished ground because of site slope.

Floor area ratio: the ratio of the sum of all constructed floor areas to the plot area. Basements, mezzanines, habitable roof spaces and open or enclosed projections are included; areas excluded from the ratio are deducted.

Clause 4(5) — often missed Both ratios are computed on the net plot area (as amended 25/7/2019). Areas excluded from the floor area ratio are listed in Clause 22: lift shafts, fire stairs and lobbies, light wells, shelters, parking and so on — each with its own conditions.

2. Lifts — Clause 34

StoreysRequirement
3 storeysa lift shaft must be provided
4 storeys and abovea lift must be installed
Habitable basements count. Single-dwelling houses are outside this requirement.
Lift typeCar short sideCar areaDoor clear width
Building with a single lift≥ 1.20 m≥ 1.80 m²≥ 0.90 m
10 storeys and above — goods/stretcher≥ 1.20 m≥ 2.52 m²≥ 1.10 m
In buildings of 10 storeys and above at least one lift must be able to carry goods and a stretcher.
When more than one lift is required Public buildings with a floor area over 800 m² and more than 3 storeys · buildings of 10 storeys and above under the development plan · buildings with more than 20 dwellings above ground.

Clause 31: the landing onto which the lift door opens must be ≥ 1.20 m for sliding doors and ≥ 1.50 m for outward-opening doors.

3. Stairs — Clause 31

2a + b = 0.60 to 0.64 m a = riser height, b = tread depth. Tread depth ≥ 0.27 m.
BuildingMax riser height
Buildings without a lift0.16 m
Buildings with a lift0.18 m
The riser limit depends on whether there is a lift — this must be known before starting.
Winder stairs The tread must be ≥ 0.10 m at the inner edge and ≥ 0.27 m at mid-width; nosings must not project.

Common stair flight and landing widths in dwellings are computed under the fire code.

4. Ramps — Clause 30(12)

The binding ramp gradients are here, in public law. TS 9111 also covers ramp gradients; where the two differ, the regulation in force governs.

RiseMax gradientPercentMin ramp run
loading…
Band limits are inclusive. A ramp run may not exceed 900 cm; beyond that it is divided by an intermediate landing.
Other ramp dimensions Clear width ≥ 90 cm (≥ 100 cm in public buildings) · landings ≥ 150 × 150 cm · handrails at two levels, 90 cm and 70 cm, graspable at 32–45 mm diameter · kerb ≥ 5 cm on any unprotected side.

Where the rise exceeds 15 cm or the horizontal run exceeds 200 cm, guardrails are required on both sides; ramps wider than 300 cm need a central handrail.

The footprint is larger than intuition suggests: a rise of 80 cm needs at least 13.33 m of ramp, which exceeds the 9 m limit and therefore requires an intermediate landing; with landings it occupies 17.83 m on plan. The ramp simulation shows this live.

5. Minimum room sizes — Clause 29

RoomMin short sideMin clear area
loading…
Hall and corridor widths ≥ 1.20 m. Door heights ≥ 2.10 m (Clause 39).
Daylighting — an honest gap No fixed window-to-floor area ratio (such as 1/8 or 1/10) could be found in the zoning regulation currently in force. Daylighting is regulated through minimum room dimensions, the requirement for openable windows, and light-well rules.

Such a ratio may exist in the superseded regulation for unplanned areas or in local municipal by-laws. This page and the corresponding tool do not invent one.

Light-well rule: at most 4 rooms per storey may draw light from one minimum-size light well or air shaft; an air shaft is at least 0.60 × 0.60 m. In wet rooms without mechanical ventilation, the ventilation window must be ≥ 0.30 × 0.30 m clear.

6. Parking demand

UseParking requirement
loading…
Parking Regulation (OG 22/2/2018-30338) Annex 1. Unit parking area: car ≥ 20 m², bus/lorry ≥ 50 m².
Superseded value warning The 2005/2006 parking regulation used "1 per 3 flats" for dwellings and "1 per 30 m²" for shops and offices. Those are superseded. The system in force came with the 2018 amendment and is based on flat size for dwellings. Municipal PDFs showing the old table are still online.

Electric vehicles: new buildings whose minimum required parking is 20 spaces or more must provide 5% as EV charging spaces (from 1/1/2023).