Ana Sayfa / Code Reference / Fire Code — Escape and Compartments
Turkish Fire Code — Escape Routes and Fire Compartments
The escape and compartment provisions of the Turkish Regulation on Fire Protection of Buildings (BYKHY), with clause numbers. Every table below is read live from the calculation engine, so the reference and the tool cannot drift apart.
The Turkish fire regulation is public law published in the Official Gazette; its clause text and tables may be reproduced here in full.
To see the tables by playing with them: the escape route simulation shows how the required width changes with use class and area, and the compartment simulation shows why the Annex 4 footnotes give entirely different outcomes per occupancy.
1. Occupant load — Annex 5/A
The occupant load of a space is found from the area per person for its use class. The first four rows use net area, the rest gross area — miss this distinction and the occupant count is wrong from the start.
| Use | m²/person | Area basis |
|---|---|---|
| loading… | ||
2. Exit width — Clauses 32-33
If the calculated width falls below the minima, the minimum governs:
| Case | Minimum width |
|---|---|
| Any exit or escape stair | 80 cm |
| Escape route also used as corridor or hall | 110 cm |
| Occupant load 50 – 500 | 100 cm |
| Occupant load 501 – 2000 | 150 cm |
| Occupant load 2001 and above | 200 cm |
| Escape routes and stairs in high-rise buildings | 120 cm |
3. Persons per unit width — Annex 5/B
For the same storey the four escape route types have different capacities. Stair capacity is the lowest, so the required width is usually governed by the stair.
| Occupancy class | Final exit door | Other door | Escape stair | Ramp / corridor |
|---|---|---|---|---|
| loading… | ||||
4. Maximum travel distances — Annex 5/B
| Occupancy class | One-way escape | Two-way escape | ||
|---|---|---|---|---|
| unsprinklered | sprinklered | unsprinklered | sprinklered | |
| loading… | ||||
Clause 32(5): the straight-line distance may not exceed 2/3 of the permitted travel distance.
Within a dwelling, furthest point to exit door ≤ 20 m (sprinklered ≤ 30 m). From the foot of the escape stair to the open air ≤ 10 m (sprinklered ≤ 15 m).
5. Number of exits — Clause 32
| Occupant load | Minimum exits |
|---|---|
| General rule | 2 |
| Above 500 | 3 |
| Above 1000 | 4 |
In an undivided single space requiring two exits, the separation between them may not be less than 1/2 of the diagonal when unsprinklered, or 1/3 when sprinklered.
6. Fire compartments — Clause 24 and Annex 4
Definition (Clause 4): a zone enclosed on all sides by at least 60 minutes' fire resistance.
| Occupancy class | Base area | Footnote | With systems |
|---|---|---|---|
| loading… | |||
(2) With suitable systems, unlimited.
(3) If single-storey, or with suitable systems, unlimited.
(4) Excluding wholesale produce and fish markets and similar.
Clause 24(4): in non-residential buildings over 21.50 m and residential buildings over 30.50 m in height, a compartment above that height may span at most 3 storeys.
7. Four common mistakes
- Confusing net and gross area. The first four rows of Annex 5/A want net area, the rest gross. The wrong basis misleads the occupant count and hence the width.
- Sizing for one escape route only. The four routes have different capacities and the stair is the lowest. Looking only at the final exit door leaves the stair too narrow.
- Reading a travel distance without stating sprinkler provision. For offices the four cases are 15 / 30 / 45 / 75 m — a five-fold spread.
- Applying the single-exit exception partially. All three conditions are required; if one fails, two exits are needed.